motor power kW | 7.5 kW at 220...230 V AC 50/60 Hz (AC-3) 15 kW at 380...400 V AC 50/60 Hz (AC-3) 15 kW at 415...440 V AC 50/60 Hz (AC-3) 18.5 kW at 500 V AC 50/60 Hz (AC-3) 18.5 kW at 660...690 V AC 50/60 Hz (AC-3) 7.5 kW at 400 V AC 50/60 Hz (AC-4) 7.5 kW at 220...230 V AC 50/60 Hz (AC-3e) 15 kW at 380...400 V AC 50/60 Hz (AC-3e) 15 kW at 415...440 V AC 50/60 Hz (AC-3e) 18.5 kW at 500 V AC 50/60 Hz (AC-3e) 18.5 kW at 660...690 V AC 50/60 Hz (AC-3e) |
---|
motor power hp | 2 hp at 115 V AC 50/60 Hz for 1 phase motors 5 hp at 230/240 V AC 50/60 Hz for 1 phase motors 7.5 hp at 200/208 V AC 50/60 Hz for 3 phases motors 10 hp at 230/240 V AC 50/60 Hz for 3 phases motors 20 hp at 460/480 V AC 50/60 Hz for 3 phases motors 30 hp at 575/600 V AC 50/60 Hz for 3 phases motors |
---|
pole contact composition | 3 NO |
---|
contact compatibility | M4 |
---|
protective cover | With |
---|
auxiliary contacts type | Type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1 type mirror contact 1 NC conforming to IEC 60947-4-1 |
---|
auxiliary contact composition | 1 NO + 1 NC |
---|
[Ui] rated insulation voltage | Power circuit: 690 V conforming to IEC 60947-4-1 Power circuit: 600 V CSA certified Power circuit: 600 V UL certified Signalling circuit: 690 V conforming to IEC 60947-1 Signalling circuit: 600 V CSA certified Signalling circuit: 600 V UL certified |
---|
[Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947 |
---|
overvoltage category | III |
---|
[Ith] conventional free air thermal current | 10 A (at 60 C) for signalling circuit 50 A (at 60 C) for power circuit |
---|
Irms rated making capacity | 140 A AC for signalling circuit conforming to IEC 60947-5-1 250 A DC for signalling circuit conforming to IEC 60947-5-1 550 A at 440 V for power circuit conforming to IEC 60947 |
---|
rated breaking capacity | 550 A at 440 V for power circuit conforming to IEC 60947 |
---|
associated fuse rating | 10 A gG for signalling circuit conforming to IEC 60947-5-1 63 A gG at <= 690 V coordination type 1 for power circuit 63 A gG at <= 690 V coordination type 2 for power circuit |
---|
time constant | 28 ms |
---|
control circuit type | DC standard |
---|
coil technology | Built-in bidirectional peak limiting diode suppressor |
---|
control circuit voltage limits | 0.1...0.25 Uc (-4070 C):drop-out DC 0.7...1.25 Uc (-4060 C):operational DC 1...1.25 Uc (6070 C):operational DC |
---|
average impedance | 2 mOhm - Ith 50 A 50 Hz for power circuit |
---|
power dissipation per pole | 2 W AC-3 5 W AC-1 2 W AC-3e |
---|
minimum switching current | 5 mA for signalling circuit |
---|
minimum switching voltage | 17 V for signalling circuit |
---|
non-overlap time | 1.5 ms on de-energisation between NC and NO contact 1.5 ms on energisation between NC and NO contact |
---|
maximum operating rate | 3600 cyc/h 60 C |
---|
inrush power in W | 5.4 W (at 20 C) |
---|
hold-in power consumption in W | 5.4 W at 20 C |
---|
insulation resistance | > 10 MOhm for signalling circuit |
---|
tightening torque | Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat 6 mm Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2 Power circuit: 2.5 N.m - on screw clamp terminals - with screwdriver flat 6 mm Power circuit: 2.5 N.m - on screw clamp terminals - with screwdriver Philips No 2 Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver pozidriv No 2 Power circuit: 2.5 N.m - on screw clamp terminals - with screwdriver pozidriv No 2 |
---|
mounting support | Plate Rail |
---|
electrical durability | 1.65 Mcycles 32 A AC-3 at Ue <= 440 V 1.4 Mcycles 50 A AC-1 at Ue <= 440 V 1.65 Mcycles 32 A AC-3e at Ue <= 440 V |
---|
mechanical durability | 30 Mcycles |
---|
safety reliability level | B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 |
---|
operating altitude | 0...3000 m |
---|
compatibility code | LC1D |
---|
product certifications | GL BV CSA DNV LROS (Lloyds register of shipping) CCC RINA GOST UL UKCA |
---|